Nec Floor Receptacle Conference Room

Once again all 15a and 20a 125v receptacles installed within a dwelling unit crawl space 210 8 4 or in each unfinished portion of a basement not intended as a habitable room but used for storage or as a work area 210 8 5 must be gfci protected.
Nec floor receptacle conference room. From any fixed wall for each 215 sq. This receptacle shall be located at a distance not less than 6 0 from any wall. This new code reference 210 71 meeting rooms is found in article 210 branch circuits part iii. All questions and answers are based on the 2011 nec.
However if the meeting room is at least 12 0 wide and has a floor area of at least 215 square feet one receptacle outlet will be required in the floor. Receptacles must be installed so that no point measured horizontally along the floor line in any wall space is more than 6 feet or 1 8 meters from an outlet in that space. Or major portion of floor space. One floor receptacle will be required for each 215 square foot portion of the floor space.
A floor receptacle outlets are not counted as the required receptacle wall outlet if they are located more than 18 in. Shall have at least one receptacle outlet located in the floor at a distance not less than 6 ft. From the wall 210 52 a 3. 2 floor receptacle outlets.
The nec now requires floor receptacle outlets based on open floor space for meeting rooms that are at least 12 feet wide and have a floor area of at least 215 square feet. A meeting room that is at least 3 7 m 12 ft wide and that has a floor area of at least 20 m 2 215 ft 2 shall have at least one receptacle outlet located in the floor at a distance not less than 1 8 m 6 ft from any fixed wall for each 20 m 2 215 ft 2 or major portion of floor space. Floor receptacle requirements in 210 71 b 2 state that a meeting room that is at least 12 feet wide with a floor area of at least 215 square feet shall have at least one receptacle outlet located in the floor at a distance not less than 6 feet from any fixed wall for each 215 square feet or major portion of floor space. Ft take 432 divided by.
Following the floor line from a doorway fireplace or similar opening the maximum distance to a receptacle is 6 feet 1 8 meters. This new requirement will help serve today s trend that requires we travel with a myriad of electronic devices to meet our daily personal and business needs. Wide and that has a floor area of at least 215 sq. Additionally the code requires at least one receptacle for each 215 square feet of floor space or major portion thereof.
Since the meeting rooms are 432 sq.